· To test the air
conditioning, the outside
temperature should be above
60°
for 48 hours (some
manufacturers recommend 65°). If
you turn the air conditioning
system on when the
temperature is below 60°, you
may damage the compressor.
· Turn the fan switch to
"auto" and set the
thermostat below the room
temperature (76° to 78° is
recommended). The fan and
condensing unit should come
on, unless there is a time
delay, which may slow its
start.
· Let the system run for
eight to ten minutes to
balance the temperature in
the ductwork. Check the
temperature at the supply and
return registers. The
temperature at the supply
register should be 14° to 20°
Fahrenheit cooler than at the
return ducts or current room
temperature.
* If the temperature
differential is more than 20°, it
indicates restricted air.
This points to three possible
problems: 1) a dirty filter,
2) improper ductwork, or 3) a
fan that is sized wrong, not
working properly, or moving
too slowly.
· If it is less than 14°
differential, the possible
causes are 1) refrigerant
loss, 2) a dirty coil, 3) a
laboring compressor, 4) an
oversized fan, or 5) a
deficient return air system.
· There are two copper
lines going from the
condensing unit on the
exterior to the air handler
on the interior. The smaller
line is the liquid or
high-pressure line and will
be warm, not hot, to the
touch when it is operating
properly. The larger line
covered with insulation is
the suction or low pressure
line and will be cold to the
touch. The suction line
should be
"sweating" or
condensing, the way a glass
of iced tea
"sweats." It should
not be forming
"ice."
The refrigerant in the
system may be low from a
possible leak. The leak
should be located, repaired,
and recharged.
Compressor failure is a
problem, which usually
requires replacement of the
unit. Usually when a
compressor is replaced, the
entire condensing unit on the
exterior is replaced. The
typical life expectancy of a
compressor in a central air
conditioning system is 8 to15
years, depending on
geographic location.
When discussing air
conditioning system
efficiencies, the SEER number
is the typical guideline, and
the higher the SEER number,
the more efficient the unit
(E.g., a 12 SEER unit is 20%
more efficient than a 10 SEER
unit). This information can
be a considerable help when
evaluating the cost versus
the value of a new system.